Application : Water distribution network.
Working temperatures :
Cold water : Maximum 50°C.
Hot water : Maximum 90°C.
PMS : 16 bars
Specifications :
Brass body / Single jet turbine.
Inlet strainer.
Protection against the magnetic external agents.
Orientable dial.
Prepared for pulse sensor: 10L for Ref. 940EF and 942EC.
Prepared for Wireless M-Bus compact radio module or M-Bus wire module.
Installations
Horizontal or vertical.
Q3/Q1 report : Horizontal = 80 and Vertical = 50.
Connection : Male.
Agreements & tests:
Consistent with the standard EN14154.
Certified MID MI001 according to 2004/22/CE.
ACS.